What are the precautions for the design of exhaust system of Diesel generator
exhaust system
The exhaust of Diesel generator is not only harmful but also high temperature, so the design of exhaust system should be paid special attention
If the back pressure of the exhaust system on the engine exceeds the specified value, the performance of the engine will be affected and the maintenance interval will be shortened
The shorter the exhaust system, the smaller the resistance (and back pressure), and the bending parts within the system have a significant impact on the resistance. The maximum allowable resistance of the exhaust system is
R=450 mmH20: All models except SR.6D
600 mmH20: SR
816 mmH20: 6D
The resistance is measured at the outlet of the turbocharger
The recommended material for the exhaust pipe is carbon steel pipe (non galvanized)
1.1 Calculation of exhaust resistance and determination of exhaust pipe diameter
The exhaust resistance is affected by exhaust pipelines and silencers, etc
The exhaust resistance of the pipeline is obtained from the following equation
Pipe Diameter
Insisde Diameter
External Diameter
A
B
150
200
250
300
350
400
450
500
6
8
10
12
14
16
18
20
155.2
204.7
254.2
304.7
339.8
390.6
441.4
492.2
165.2
216.3
267.4
318.5
355.6
406.4
457.2
508.0